Greenheck Sidewall, Rooftop and Centrifugal Inline Ventilation Units
Check against the official notice below — it lists the full affected range.
Greenheck Fan Corp. is recalling certain ventilation units manufactured between August 11, 2004 and April 29, 2005 because the LUX 3/8-inch spinlock bolts supplied with them may not have been properly heat treated. If these bolts break during rooftop installation or after the unit is installed, the ventilation unit or its components could fall and injure people nearby.
The affected units are Sidewall, Rooftop, and Centrifugal Inline ventilation units with model numbers RBU, RBUMO, RDU, RB/R, SB/S, and BSU 360-420 and serial numbers 04HXXXXX through 05DXXXXX (model and serial numbers are listed on the unit's metal identification plate). According to the recall announcement, LUX spinlock bolts in affected units will be replaced at no cost to the end user, but the source does not specify how consumers should contact Greenheck Fan Corp. to arrange this replacement.
Written by software from the official notice below. Not reviewed by a lawyer.
LUX 3/8-inch spinlock bolts supplied with these units may not have been properly heat treated, which can result in the bolts breaking. Bolt failure during lifting for rooftop installation or after installation could cause the unit or components to fall and injure bystanders.
LUX spinlock bolts in affected units will be replaced at no cost to the end user.
Affected units are Sidewall, Rooftop and Centrifugal Inline ventilation units built between August 11, 2004 and April 29, 2005, containing 16-thread-per-inch 3/8-inch by ¾-inch spinlock bolts with LUX head markings. Affected model numbers are RBU, RBUMO, RDU, RB/R, SB/S, and BSU 360-420 with serial numbers 04HXXXXX through 05DXXXXX. The model and serial numbers are found on metal identification plate on the units.