CPSC, Trane Company Announce Recall of Voyager Heating and Air Conditioning Systems

Is my product affected?

Trane Voyager Series Combination Gas Furnace and Electric Air Conditioning Units

  • Brand The Trane Company, of Tyler, Texas, a division of American Standard Companies Inc.

Check against the official notice below — it lists the full affected range.

What happened

Trane Company and the CPSC are recalling certain Voyager series light commercial rooftop air conditioning systems installed in schools and commercial buildings. One of the three internal flue gas tubes in these units can separate from the heat exchanger, allowing flue gases including carbon monoxide to enter the building's airstream, which could cause serious injury or death. The recalled units were manufactured between June 1, 2000 and August 16, 2000, have serial numbers beginning with R21 through R33, and include various model numbers such as YCD036C1H, YCD060CWH, YCD048C1H, YCH060C1H, YCH048C1H, YCH060C3H, YCD060C1H, YCH060C4H, YCD060C3H, and YCD060C4H. You can locate your unit's model and serial number on the nameplate on the outside sheet metal at the end of the unit where the propeller fan is visible on top, directly to the left of the exposed outdoor coils.

Consumers with recalled units should call their local independent Trane or American Standard dealer to arrange a free inspection and replacement if needed. Trane will completely replace the heat exchanger end plate and internal flue gas tube assemblies in all recalled units at no cost to the consumer.

Written by software from the official notice below. Not reviewed by a lawyer.

Hazard

One of the three internal flue gas tubes extending from the heat exchanger can separate from the heat exchanger. This could allow flue gases, including carbon monoxide, to enter the building airstream. This could result in serious injury or death to building occupants.

What should I do?

Call the local independent Trane or American Standard dealer for a free inspection and replacement, if needed. Trane will completely replace the heat exchanger end plate and internal flue gas tube assemblies in all recalled units at no cost to the consumer.

Details from the source

The Voyager series of light commercial rooftop air conditioners with electric cooling and gas-fired heat exchangers, which are installed in schools and commercial applications, have 120,000 to 135,00 BTU heating capacity and three- to five-ton cooling capacity in horizontal and downflow configurations. The Voyager series has been manufactured by Trane since 1988 and is distributed under the Trane® and American Standard® brand names. The recalled units were manufactured between June 1, 2000 and August 16, 2000 and have serial numbers beginning with R21 through and including R33. The recalled products include the following model designations: YCD036C1H_ _ _ YCD060CWH_ _ _ YCD048C1H_ _ _ YCH060C1H_ _ _ YCH048C1H_ _ _ YCH060C3H_ _ _ YCD060C1H_ _ _ YCH060C4H_ _ _ YCD060C1H_ _ _ YCD060C3H_ _ _ YCD060C4H_ _ _ A name plate bearing each unit's model and serial number is located on the outside sheet metal at the end of the unit where the propeller fan is visible on top, directly to the left of the exposed outdoor coils.

Source

Official record: U.S. Consumer Product Safety Commission ↗

Republished from the official source above; details can change — the source record controls.

Related recalls

All U.S. Consumer Product Safety Commission recalls

Hurt by this product? Start a free Case Check

ProductRisk is not a law firm and does not provide legal services or legal advice. ProductRisk is a free consumer product-safety information service operated by Plaintify, Inc., a technology company. If you ask to be connected with a law firm, any legal services are provided by that firm — not by ProductRisk or Plaintify.

Privacy · Plaintify