← Search recalls
U.S. Consumer Product Safety CommissionRecalled 2017-05-12

Honeywell International Recalls SWIFT® Wireless Gateway Sold with Fire Alarm Systems Due To Failure to Communicate in Fire

Is my product affected?

SWIFT wireless gateway sold with fire alarm systems

  • Brand Honeywell International Inc., of Northford, Conn.

Check against the official notice below — it lists the full affected range.

What happened

Honeywell is recalling SWIFT wireless gateways sold with fire alarm systems. These gateways are round, white devices measuring eight inches in diameter that serve as the connection between fire alarm control panels and smoke detectors in commercial buildings such as offices, hotels, industrial facilities, and apartment complexes. The gateways have failed to properly communicate with connected smoke detectors when significant environmental contaminants are present, which could prevent the detectors from alerting occupants to a fire.

The recalled gateways are sold under multiple brand names including Notifier, Fire-Lite, Gamewell-FCI, Honeywell, and Johnson Controls, with model numbers FWSG, W-GATE, VW-GATE, XLS-WSG, and JFWSG and date codes ranging from 13/14 through 12/15/16 printed on the back of the device. Affected consumers should contact Honeywell to obtain a firmware update for the SWIFT wireless gateway installed on their system. Commercial building customers should continue using the recalled detectors until the firmware update is completed.

Written by software from the official notice below. Not reviewed by a lawyer.

Hazard

The smoke detectors connected to the gateway can fail to activate properly when significant environmental contaminants are present, posing a risk that consumers will not be alerted to a fire.

What should I do?

Contact Honeywell for an update of the firmware on the SWIFT wireless gateway(s) installed on the system. Commercial building customers should continue using the recalled detectors until the firmware is updated.

Details from the source

This recall involves the SWIFT wireless gateway sold with fire alarm systems. The gateways are round, white and measure eight inches in diameter. The gateways are the bridge between the fire alarm control panel and the detectors. These systems are used primarily for indoor or covered areas in commercial buildings, such as in office buildings, hotels, industrial facilities, and apartment complexes. The model number and date codes are printed on the back of the gateway on a white label on the circuit board. The gateways have the following brand names, model numbers and date codes. Brand Model Date Code Range NOTIFIER FWSG 10 13 14 through 12 15 16 Fire-Lite W-GATE Gamewell-FCI VW-GATE Honeywell XLS-WSG Johnson Controls JFWSG

Source

Official record: U.S. Consumer Product Safety Commission ↗

Republished from the official source above; details can change — the source record controls.

Related recalls

All U.S. Consumer Product Safety Commission recalls

Hurt by this product? Start a free Case Check

ProductRisk is not a law firm and does not provide legal services or legal advice. ProductRisk is a free consumer product-safety information service operated by Plaintify, Inc., a technology company. If you ask to be connected with a law firm, any legal services are provided by that firm — not by ProductRisk or Plaintify.