Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)
Check against the official notice below — it lists the full affected range.
Gamewell-FCI is recalling ILI-MB-E3 and ILI-S-E3 fire alarm panels installed in commercial buildings. The panels can become non-responsive under certain configurations, which would prevent connected detectors from detecting and responding to fires, smoke, or carbon monoxide alarms. The issue occurs only when a Signaling Line Circuit includes at least two specific detector types (Acclimate, 4-Warn, Photo/CO, or iFAAST) addressed within the same FlashScan polling group.
Affected consumers should immediately contact their distributor to obtain a free firmware upgrade to repair the panels. The record does not specify additional details about contacting the distributor or what identifying information may be needed.
Written by software from the official notice below. Not reviewed by a lawyer.
When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.
Consumers should immediately contact the distributor to obtain the free repair, a firmware upgrade.
This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.